nvidia gb200 cooling
NVIDIA GB200 NVL72 cooling requirements
Supply temps, flow rates, manifold spec and CDU sizing for GB200 NVL72 racks — from a crew that has commissioned them.
12 min read Updated 2026-06-18 Field-verified
The GB200 NVL72 rack is 132 kW of compute in a single tile. This is what our crews specify, install and commission for it — no marketing filler.
Thermal load per rack
- 72 × Blackwell GPUs + 36 × Grace CPUs, direct-to-chip cooled.
- Total design load: 120–132 kW/rack.
- DLC captures ~85%; residual ~20 kW to air (NVSwitch trays, PSUs, ToR).
Coolant and loop spec
- Coolant: demineralised water + OEM inhibitor. PG25 only where freeze is a real risk.
- Supply temp: 32–40 °C at the rack inlet.
- ΔT: 10 K design, 12 K trip.
- Flow: ~3.1 L/s per rack at 10 K.
- Filtration: 50 μm at CDU inlet, 5 μm inline.
CDU and manifold
Plan one L2L CDU per 6–8 racks (approximately 800–1,000 kW rated). Manifold material: stainless with EPDM-sealed dripless quick-disconnects. Every rack drop gets an isolation valve, flow meter and leak rope.
Commissioning gates
- Hydrostatic test at 1.5× MAWP for 4 h, zero pressure drop.
- Chemical passivation and 24 h air-separator run.
- Loop de-aeration verified by clear-sight glass.
- Full-load ΔT sweep at 25/50/75/100%.
- Simulated pump trip, CDU failover under load.
- Leak-rope end-to-end test with distilled water on tray.
Field gotchas
- Under-sized expansion tanks pop relief valves during first warm-up.
- Mixed-metal manifolds without dielectric unions corrode within 12 months.
- QD misalignment on hot-swap causes seep leaks — torque the rack rails first.
- Facility water TDS above 150 ppm fouls the CDU heat exchanger in a season.
Need immediate hydronic support?
Critical leak response, pump diagnostics, and pressure stabilization. Engineers en route in under 4 hours.